User Tools

Site Tools


construction:quality_assurance:thermal_bridges

This is an old revision of the document!


Quality Assurance - Thermal bridges

The parts of the building envelope in which higher transmission losses occur relative to the surface are referred to as thermal bridges. With moderate detail formation, these transmission losses are between 10 and 20%. In unfavourable cases they may even be 30%. The effects can be serious in terms of the low temperatures of the interior surfaces and the resulting problems with mould growth, and impairing the general level of comfort and health that the building can offer.

In the German energy regulations (EnEV), overall thermal bridge losses are calculated with an addition of ΔUWB = 0.1 W/(m²K) to the U-value; in compliance with the standard details given in the DIN 4108 (Supplementary Sheet 2) this is 0.5 W/(m²K). For refurbishments, however, these values can only be used for newly built. Almost invariably, unfavourable thermal bridge factors can be expected, particularly for existing connection details at the plinth and for connections of the inner wall to the unheated basement or to the floor slab. In these cases, where it is difficult to remove the cause of the thermal bridge, it is necessary to extend the heat flow path and thus improve the thermal bridge loss coefficient.

When planning an energy-efficient modernisation, it is strongly recommended that all thermal bridges be included, along with their lengths. The respective thermal bridge loss coefficients (Ψ or Psi-values) must either be calculated or else taken from thermal bridge atlases or other sources. For detailed calculations of thermal bridges typical in masonry multi-family houses built in the 1950s and 1960s, the resulting value for ΔUWB is between 0.02 and 0.03 W/(m²K), if great care is taken to reduce thermal bridges. In comparison, optimised new Passive House buildings have a ΔUWB value between 0.01 and negative 0.01 W/(m²K). In favourable cases, these specific values can be achieved for renovations in the area above the plinth if all connection details are redone.

Reference will be made to the respective thermal bridge aspects of each construction detail and solutions will be presented. In the following illustration, examples of detail points are presented for a building that was built in 1930.

abb_1a_thermal_bridges_quality_assurance.jpgabb_1b_thermal_bridges_quality_assurance.jpgConnection of basement to external wall:
the insulation has been embedded only 25cm
into the ground for financial reasons;
in addition, a frost apron has been laid
along the outside;
Ψa = 0.134W/(mK)
abb_2a_thermal_bridges_quality_assurance.jpgabb_2b_thermal_bridges_quality_assurance.jpgConnection of internal celler wall to
brickwork on the ground floor:

due to the vertical continuation of the
basement wall insulation downwards
(30cm), a Ψ a of 0.30W/(mK)
was achieved; for walls with a thickness
of 38cm, this Ψa = 0.46W/(mK)
abb_3a_thermal_bridges_quality_assurance.jpgabb_3b_thermal_bridges_quality_assurance.jpgKnee wall:
Completely insulating the knee wall
with a thickness of 20cm laterally
and 10cm above gave a
Ψa = 0.056W/(mK)
abb_4a_thermal_bridges_quality_assurance.jpgabb_4b_thermal_bridges_quality_assurance.jpgWindows:
thermal bridges comparable to the situation
in a new build with Ψa = 0.017W/(mK)
for the connection detail on the side;
the lower area of the metal window sill has
Ψa = 0.030W/(mK)

Illustration 1: (source: left PHI, right Schulze Darup)

Illustration 2: Infrared thermographic image after completion of the exterior thermal insulation compound system, before installation of the balcony: the four reinforcing attachment points of the balcony can be seen as well as the traces of the attachment of the temperature sensor under the ground floor window on the right. For comparison: on the right side of the thermographic image there is a similar but non-renovated existing building (source: PHI)
Illustration 3: Thermographic image of the inside of the ground floor base area at a corner of the building (source: PHI)

Quality assurance with respect to thermal bridge effects initially takes place by optimising the details based on the calculation of the thermal bridges. The purpose of construction planning is to meticulously examine the building for any possible thermal bridges effects. Studying a cross-section is not enough; three-dimensional problematic areas and point thermal bridges must also be checked. For the connection details, e.g. of windows, detailed examinations should be carried out regarding the profiles and window glass edge systems as well as the installation situation.

In the process of tendering, the characteristics of the building components in relation to the thermal bridge parameters should also be described and components should be checked before installation so as to see if they fit the description.

An inspection with infrared thermographic imaging, which makes the infrared radiation visible in a series of colours, can be carried out to assess the thermal building envelope. The following illustrations show infrared images of the same building after completion of the energy-efficient modernisation.

Illustration 4: The thermographic image shows warm surfaces for the glazing, frames and external wall as well as the thermal bridge at the glass edge system. The base point thermal bridge below at the transition of the external wall and basement ceiling can also be seen. (source: PHI)


A particularly interesting aspect is the comparison of the thermographic imaging with the set values of the thermal bridge calculation. It is important that the respective boundary conditions that exist are also compared in the process. The set values of the thermal bridge calculation are compared with the measured values of the thermographic images using two examples for the building’s base.



external_wallbasement_ceiling_set_temp._thermal_bridges_quality_assurance.jpgexternal_wallbasement_ceiling_thermal_bridges_quality_assurance.jpgExternal wall/basement ceiling:
at the lower edge of the insulation apron,
the set temperature is slightly lower
(reason: cooling of the basement
during the construction period)
external_wall_at_base_set_temp._thermal_bridges_quality_assurance.jpgexternal_wall_at_base_thermal_bridges_quality_assurance.jpgExternal wall at base on the ground floor:
The set temperatures and measured
temperatures match; the temperature
is 1.5K lower in the corner of the room,
as expected.

Illustration 5 (source: PHI)

See also

construction/quality_assurance/thermal_bridges.1510924324.txt.gz · Last modified: 2017/11/17 14:12 by kdreimane