planning:building_services:ventilation:ventilationdusts
Differences
This shows you the differences between two versions of the page.
| Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
| planning:building_services:ventilation:ventilationdusts [2024/10/28 16:20] – [Ventilation ducts under the exterior insulation] yaling.hsiao@passiv.de | planning:building_services:ventilation:ventilationdusts [2024/10/29 09:15] (current) – removed yaling.hsiao@passiv.de | ||
|---|---|---|---|
| Line 1: | Line 1: | ||
| - | ====== Ventilation Ducts within the insulation layer ====== | ||
| - | ===== Ventilation ducts under the exterior insulation ===== | ||
| - | If old buildings are equipped with ventilation systems with heat recovery as part of a refur-bishment, | ||
| - | The heat recovery unit can be located either outside the thermal envelope, e.g. in an uncon-ditioned attic, or inside the building / the flats. | ||
| - | This type of installation results in additional transmission heat losses. It must also be taken into account that the air flowing in the ducts changes its temperature, | ||
| - | |||
| - | [{{ : | ||
| - | |||
| - | Figure 1 shows a section through a ventilation duct which is installed in the thermal insulation on the masonry, as described. Three temperatures are involved in the resulting heat flows: | ||
| - | * the internal temperature Ti, | ||
| - | * the external temperature Ta | ||
| - | * the temperature in the duct Tair. | ||
| - | |||
| - | As shown in the illustration, | ||
| - | |||
| - | In the following calculations, | ||
| - | |||
| - | [{{ : | ||
| - | |||
| - | On this basis, a situation such as shown in Figure 2 can now be analysed in more detail. Different heat flows arise: the warm extract air with temperature T< | ||
| - | |||
| - | In order to understand the influence of this situation on the transmission and ventilation losses of the building, it is helpful to precisely analyse the heat flows. On this basis, simplifica-tions can then be made for practical application. | ||
| - | |||
| - | First of all, it should be assumed that T< | ||
| - | |||
| - | {{ : | ||
| - | |||
| - | This temperature will subsequently be referred to as the equilibrium temperature T< | ||
| - | The (two-dimensional) overall heat loss per metre of wall or duct length through the internal surface of the wall will then be | ||
| - | |||
| - | {{ : | ||
| - | |||
| - | With reference to the external surface, the same value results in the form | ||
| - | |||
| - | {{ : | ||
| - | |||
| - | The temperature of the air flowing inside the duct becomes similar to the equilibrium tem-perature exponentially. For instance, the following applies for the extract air duct | ||
| - | |||
| - | {{ : | ||
| - | |||
| - | in which m ̇c_p is the thermal capacity current in the ventilation duct. | ||
| - | At the connecting piece of the ventilation unit, after passing through the duct length l, the extract air still has the temperature | ||
| - | |||
| - | {{ : | ||
| - | |||
| - | Also, at the connecting piece of the ventilation unit, the following supply air temperature is thus calculated by | ||
| - | |||
| - | {{ : | ||
| - | |||
| - | where η_HR is the heat recovery efficiency of the ventilation unit on the supply air side. | ||
| - | |||
| - | The supply air temperature on the inside can be determined in a way similar to that for the extract air temperature. | ||
| - | |||
| - | With the help of these interrelationships, | ||
| - | |||
| - | [{{ : | ||
| - | |||
| - | {{ : | ||
planning/building_services/ventilation/ventilationdusts.1730128851.txt.gz · Last modified: by yaling.hsiao@passiv.de