* The wind shield coefficient is e = 0.07 (moderate shielding), the volumetric fresh air flow through gaps is therefore: | * The wind shield coefficient is e = 0.07 (moderate shielding), the volumetric fresh air flow through gaps is therefore: | ||
\\ | \\ | ||
- | {{: | + | <WRAP center 60%> |
+ | $$ | ||
+ | \Large{n_{2} = V_{Raum} \cdot n_{50} | ||
+ | $$ | ||
+ | </ | ||
\\ | \\ | ||
* The concentration of CO2 in the external air is 700 mg/m3, i.e. 360 ppm (according to CR 1752). | * The concentration of CO2 in the external air is 700 mg/m3, i.e. 360 ppm (according to CR 1752). |