planning:airtight_construction:general_principles:checklist_test_reports_of_airtightness_measurements [2022/05/03 11:16] – [Checklist: Test reports of airtightness measurements] gergina.radeva@passiv.deplanning:airtight_construction:general_principles:checklist_test_reports_of_airtightness_measurements [2023/07/18 14:33] – [See also] corinna.geiger@passiv.de
Line 1: Line 1:
-======Checklist: Test reports of airtightness measurements======+====== Checklist: Test reports of airtightness measurements ======
  
-Is the air tightness measurement protocol complete? This can be easily confirmed using this checklist: \\+Is the air tightness measurement protocol complete? This can be easily confirmed using this checklist:
  
-  *Is all general information included? +  * Is all general information included? 
-    *Tester: name, address and signature +      * Tester: name, address and signature 
-    *Object +      * Object 
-    *Date of test +      * Date of test 
-    *Device +      * Device 
-    *Measurement standard (norm) +      * Measurement standard (norm) 
-    *Inside and outdoor temperatures +      * Inside and outdoor temperatures 
-    *Wind velocity  +      * Wind velocity 
-    *Flow coefficient Cenv +      * Flow coefficient Cenv 
-    *Leakage coefficient CL +      * Leakage coefficient CL 
-  *Is the airtightness measurement performed in accordance with EN 13829 (Method A) or alternatively in accordance with ISO 9972 (Method 1)? +  * Is the airtightness measurement performed in accordance with ISO 9972 (Method 1)? 
-  *Is room-by-room calculation of the air volume of the building included? Is the calculation correct? +  * Is room-by-room calculation of the air volume of the building included? Is the calculation correct? 
-  *Has the installation location of the fan been documented? +  * Has the installation location of the fan been documented? 
-  *Has temporary sealing of the building envelope been recorded (sealing of outdoor air and exhaust air ducts at least)? +  * Has temporary sealing of the building envelope been recorded (sealing of outdoor air and exhaust air ducts at least)? 
-  *Has a series of measurements at positive pressure AND negative pressure been performed? +  * Has a series of measurements at positive pressure AND negative pressure been performed? 
-  *For each series of measurements, were 5 measuring points used at different pressure differences (highest value ± 50 Pa at least)? +  * For each series of measurements, were 5 measuring points used at different pressure differences (highest value ± 50 Pa at least)? 
-  *Is the flow exponent "n" between 0.5 and 1.0 (otherwise indicates measurement error due to a change in the envelope e.g. window opening)? +  * Is the flow exponent "n" between 0.5 and 1.0 (otherwise indicates measurement error due to a change in the envelope e.g. window opening)? 
-  *Is the average value of the natural pressure difference between -5 and 5 Pa (measurement of the pressure difference before and after each measurement series)? +  * Is the average value of the natural pressure difference between -5 and 5 Pa (measurement of the pressure difference before and after each measurement series)? 
-  *//Note:// If the wind speed is greater than 6 m/s (21.6 km/h) OR the wind force is higher than 3 Beaufort, the stated limiting values for the pressure difference will usually be exceeded. +  * //Note://  If the wind speed is greater than 6 m/s (21.6 km/h) OR the wind force is higher than 3 Beaufort, the stated limiting values for the pressure difference will usually be exceeded. 
-  *In general, the positive and negative pressure values n50 are relatively close to each other. If there are significant differences between the two results, a plausible explanation should be given in the measurement report.+  * In general, the positive and negative pressure values n50 are relatively close to each other. If there are significant differences between the two results, a plausible explanation should be given in the measurement report.
  
-**Recommendation:** leakage detection at negative pressure should be carried out before the measurements, and any large leaks should be rectified and this should be documented.\\+**Recommendation:**  leakage detection at negative pressure should be carried out before the measurements, and any large leaks should be rectified and this should be documented.
  
-**Exception:** For the measurement of tall buildings (e.g. high-rise buildings) special boundary conditions apply. Please contact your certifier or building.certification@passiv.de \\+**Exception:**  For the measurement of tall buildings (e.g. high-rise buildings) special boundary conditions apply. Please contact your certifier or building.certification@passiv.de
  
-{{ :picopen:v1.2_checklist_test_reports_of_airtightness_measurements.pdf |Checklist V 1.2: Test reports of airtightness measurements for download}} +{{:picopen:v1.2_checklist_test_reports_of_airtightness_measurements.pdf|Checklist: Test reports of airtightness measurements for download }}
-{{ :picopen:v1.2_checklist_test_reports_of_airtightness_measurements.pdf |Checklist V 1.2: Test reports of airtightness measurements for download}}+
  
-\\+==== See also ==== 
 + 
 +[[..:..:airtight_construction|Overview of the Passipedia articles on airtightness]] 
 + 
 +Record of an airtightness test:  [[:certification:certified_passive_houses:example_documents|]] 
 + 
 +[[..:airtightness_measurement_of_high-rise_buildings_guidelines|]] 
 + 
 +Click [[..:..:guides_and_aids|here]] to go back to the Guides and Aids
  