efficiency_now:building_envelope:interiorinsulation
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
efficiency_now:building_envelope:interiorinsulation [2022/10/20 12:14] – yaling.hsiao@passiv.de | efficiency_now:building_envelope:interiorinsulation [2022/12/09 02:52] (current) – [See also] yaling.hsiao@passiv.de | ||
---|---|---|---|
Line 1: | Line 1: | ||
====== Thermal protection using interior insulation ====== | ====== Thermal protection using interior insulation ====== | ||
+ | **Because interior insulation is better than you think!** | ||
- | ** * [[efficiency_now: | + | |**Quick links**|[[efficiency_now: |
- | ** * [[efficiency_now: | + | ===== Preface: exterior insulation or interior insulation? ===== |
- | + | ||
- | ** * [[efficiency_now: | + | Improved thermal protection is a crucial prerequisite for a comfortable living environment, |
+ | |||
+ | ===== Interior insulation – done properly | ||
+ | |||
+ | Interior insulation will only improve structural protection if it is carefully planned and executed. Numerous successful examples already implemented decades ago demonstrate that this works really well. | ||
+ | |||
+ | |{{: | ||
+ | |Thermographic image of an [[https:// | ||
+ | |||
+ | ===== Caution - clarification in advance is necessary, otherwise there is a risk of damage! ===== | ||
+ | |||
+ | The following prerequisites must be checked first: | ||
+ | |||
+ | - Is there any **[[https:// | ||
+ | - Is the façade to be insulated allocated to the **driving rain** stress class III? If so, then " | ||
+ | - **Leaks** (e.g. near rain gutters or water pipes) which saturate the building assembly must be repaired. | ||
+ | - **Wet building materials** (e.g. repairing plaster) must be allowed to dry out before the interior insulation is installed. | ||
+ | - Are **water-carrying pipes** (heating pipes, hot water pipes and also cold water pipes) "built into" (plastered over in) the exterior wall ((How do I determine this? The best way is to use thermographic imaging)) ((Of course, this can also be a problem even with no interior insulation in case of failure of the heating system. It is advisable to check this before the next winter!)) which is to be insulated on the inside here? If so: interior insulation should NOT be applied in these areas (strip plus or minus 1 m) if these pipes cannot be shut down and drained ((Another argument in favour of exterior insulation)). | ||
+ | |||
+ | All the problematic areas mentioned here basically have nothing to do with interior insulation - these are all problems which should be remedied in any case if homeowners are interested in long-term preservation of the building substance of their home. Considerations relating to interior insulation may then perhaps lead to such defects being rectified - this will avoid structural damage and improve comfort in addition, and in the case of otherwise damp walls, this will also already save some energy on its own. | ||
+ | |||
+ | ===== Interior insulation: airtight and thermal bridge minimised ===== | ||
+ | It is always essential to achieve the following: | ||
+ | * **[[https:// | ||
+ | * **Minimisation of thermal bridges** at all connection points of the interior insulation. | ||
+ | Why is airtightness important? With air flow behind the interior insulation, in winter huge amounts of moisture can accumulate in the wall assembly with normal indoor air coming from the old interior surface; we have explained this more exactly here: [[https:// | ||
+ | |||
+ | Unfortunately, | ||
+ | |||
+ | * //Window reveals:// with interior insulation, flanking insulation ≥ 20 mm up to the window frame is //essential // (this can also be implemented as tapered insulation if enough space is not available). | ||
+ | * // | ||
+ | * // | ||
+ | |||
+ | |{{ : | ||
+ | |**Insulation wedge**|**Flanking insulation**|**Heat conducting plate**| | ||
+ | |//**Fig. 1 solutions for reducing thermal bridges at the interior wall connection as an example.**// | ||
+ | |||
+ | * All the methods with decreasing interior insulation that tapers off as described here for the example of an interior wall should also be used in other places where the interior insulation would otherwise end " | ||
+ | |||
+ | The exact details ((Usually an " | ||
+ | **[[[[efficiency_now: | ||
+ | **[[efficiency_now: | ||
+ | |||
+ | By the way, with regard to flanking insulation at the edges, it is NOT absolutely necessary to rigidly adhere to the " | ||
+ | |||
+ | More details including many critical connection areas are described and calculated in the Protocol Volume on " | ||
+ | |||
+ | |{{ : | ||
+ | |**Insulation wedge - tapering off from approximately 25 mm to a few mm **| | ||
+ | |||
+ | An example of an interior insulation measure carried out on a DIY basis can be found here: [[https:// | ||
+ | |||
+ | ===== Solutions for protection against moisture ===== | ||
+ | The high amount of water vapour partial pressure which exists in the indoor air in winter can also cause moisture transport towards the (now cold) old wall structure behind interior insulation due also to water vapour diffusion ((Very little water vapour is actually transported here, with classic exterior walls this is about 5 g per m² per day at the most. For removing moisture out of the indoor space this does not play any role - just one person alone releases approximately 2.4 kg of water vapour into the indoor air each day. But: over the course of the year, a few grams may accumulate in an incorrectly built wall structure. This can happen especially if the water vapour gets into the wall structure easily but cannot leave it again so easily.)). There are two different concepts possible for avoiding moisture-related damage: | ||
+ | |||
+ | **Solution I** is the " | ||
+ | |||
+ | For **Solution II**, namely the **"use of capillary-active insulation materials" | ||
+ | |||
+ | Compromising on the interior insulation thickness is inevitable: the recommended insulation thickness in case of interior insulation is between 40 and 120 mm (thermal conductivity class 035 to 040 (= 0.035 to 0.040W/ | ||
+ | |||
+ | Implemented examples show that in the range of ΔUWB the " | ||
+ | |||
+ | |{{ : | ||
+ | |Potentials saving energy in existing buildings in Germany (from [AkkP 32])| | ||
+ | |||
+ | The energy savings potentials for typical existing buildings have been compiled in this illustration: | ||
+ | |||
+ | ===== What's the advantage - also in economic terms? ===== | ||
+ | |||
+ | Whether such measures also "pay off" is a key question for many people; it has almost become " | ||
+ | |||
+ | Now there is no general answer to this because there are always some extreme cases in which this is especially worthwhile (uninsulated concrete heater niches, for example) or in which it is actually not worthwhile at all (e.g. if there is an exterior wall of a Passive House building which already has 25 cm of high quality insulation). | ||
+ | |||
+ | However, wanting to know whether a measure would be worthwhile is a legitimate concern in each case. Thus we need a way to check the economic efficiency under the specific conditions existing in individual cases. | ||
+ | |||
+ | And it is precisely for this reason that we have created an easy-to-use online [[efficiency_now: | ||
+ | |||
+ | It was interesting to find out that retrofitted interior insulation pays for itself through the saved energy costs and even saves money on top of that. There are usually even some returns on the invested capital here - where else is that possible for " | ||
+ | |||
+ | This economic consideration is only half the truth, of course, because due to interior insulation, thermal comfort inside is also improved, and security for the occupants is also significantly increased in the event of a serious energy crisis: somewhat bearable conditions can then still be maintained in a room even with little energy. Those are not the only advantages. In fact, if changing to a sustainable heating system with a heat pump for example becomes necessary at some point, then with improved insulation this will often almost always make sense in the first place and will be possible with considerably less effort ((Because then only marginally better heaters will work and the output of the heat pump will be lower. | ||
+ | |||
+ | ===== See also ===== | ||
+ | |||
+ | [[efficiency_now: | ||
+ | |||
+ | [[efficiency_now: | ||
+ | |||
+ | Back to overview of [[efficiency_now: | ||
+ | |||
+ | [[efficiency_now: | ||
+ | |||
+ | [[efficiency_now: | ||
+ | |||
+ | General information on [[planning: | ||
+ | |||
+ | ===== Reference literature ===== | ||
+ | [AkkP 24]. Refurbishment with Passive House components, Protocol Volume No. 24 of the Research Group for Cost-effective Passive Houses, Phase III; Passive House Institute; Darmstadt, 2003 | ||
+ | |||
+ | [AkkP 32] Passive House components + interior insulation, Protocol Volume No. 32, Passive House Institute, Darmstadt. | ||
+ | Important results supplemented with new material can be found in PASSIPEDIA with this link: Interior insulation solutions. | ||
efficiency_now/building_envelope/interiorinsulation.1666260880.txt.gz · Last modified: by yaling.hsiao@passiv.de