basics:building_physics_-_basics:thermal_bridges:tbcalculation:ground_contact:procedure
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revision | |||
basics:building_physics_-_basics:thermal_bridges:tbcalculation:ground_contact:procedure [2016/08/16 13:22] – [Recommended procedure for calculating thermal bridges of components in contact with the ground] mschueren | basics:building_physics_-_basics:thermal_bridges:tbcalculation:ground_contact:procedure [2019/02/21 10:20] (current) – cblagojevic | ||
---|---|---|---|
Line 5: | Line 5: | ||
* taking into account the ground as a material | * taking into account the ground as a material | ||
+ | |||
* partial taking into account the ground with small layers of earth or with small blocks of earth in the calculation models | * partial taking into account the ground with small layers of earth or with small blocks of earth in the calculation models | ||
+ | |||
* no depiction of the ground, in a similar way to calculations of regular thermal bridges towards the air | * no depiction of the ground, in a similar way to calculations of regular thermal bridges towards the air | ||
+ | |||
* or the ground is depicted | * or the ground is depicted | ||
Line 21: | Line 24: | ||
* The ground must be depicted with the same length for the x and y directions in both calculation models with at least five or six times the floor slab length (see illustration). | * The ground must be depicted with the same length for the x and y directions in both calculation models with at least five or six times the floor slab length (see illustration). | ||
+ | |||
* The external dimensional reference applies for the floor slab length (in contrast to the DIN EN ISO 10211). This is recommended for a length of 4 metres. | * The external dimensional reference applies for the floor slab length (in contrast to the DIN EN ISO 10211). This is recommended for a length of 4 metres. | ||
+ | |||
* For calculation of the additional conductances, | * For calculation of the additional conductances, | ||
+ | |||
* The block of earth must exhibit adiabatic boundary conditions at the interfaces. | * The block of earth must exhibit adiabatic boundary conditions at the interfaces. | ||
basics/building_physics_-_basics/thermal_bridges/tbcalculation/ground_contact/procedure.1471346578.txt.gz · Last modified: 2016/08/16 13:22 by mschueren