====== Airtightness measurements in Passive Houses ====== | ====== Airtightness measurements in Passive Houses ====== | ||
===== Instructions for carrying out measurements ===== | ===== Instructions for carrying out measurements ===== | ||
Line 10: | Line 5: | ||
Airtightness measurements in Passive House buildings are to be carried out uniformly worldwide according to ISO 9972, method 1. The deviations (these are not of a fundamental nature), clarifications and additions to the standard in relation to Passive Houses are described here. \\ | Airtightness measurements in Passive House buildings are to be carried out uniformly worldwide according to ISO 9972, method 1. The deviations (these are not of a fundamental nature), clarifications and additions to the standard in relation to Passive Houses are described here. \\ | ||
The calculation of the reference volume for passive houses is to be carried out according to the procedure listed below which is not part of the ISO 9972. The resulting volume is to be used for the determination of the n< | The calculation of the reference volume for passive houses is to be carried out according to the procedure listed below which is not part of the ISO 9972. The resulting volume is to be used for the determination of the n< | ||
- | For the calculation and documentation, | + | For the calculation and documentation, |
==== 1. Comparison of designations ==== | ==== 1. Comparison of designations ==== | ||
Line 16: | Line 11: | ||
The superseded standards EN 13829 and the current ISO 9972 use different designations in some places. For a better overview, the most important ones are compared here: | The superseded standards EN 13829 and the current ISO 9972 use different designations in some places. For a better overview, the most important ones are compared here: | ||
- | [{{ :picprivate: | + | [{{ :picopen: |
==== 2. Calculation of volumes ==== | ==== 2. Calculation of volumes ==== | ||
- | |The air volume V< | + | The air volume V< |
- | |**Note: | + | |
- | |Irrespective of the degree of completion of the building, **the dimensions used should | + | |
- | |**A full and comprehensible room-by-room | + | |
- | + | ||
- | + | ||
- | [{{:picopen: | + | |
- | + | ||
- | \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ | + | |
- | + | ||
- | The **total air volume** within the thermal envelope will thus be taken into account. Special features are shown in Figure 2 for more detailed explanation. | + | |
- | + | ||
- | [{{: | + | |
- | \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ | + | |
- | |Visible rafters, beams, plasterboard encasings, wall-mounted installations (if these do not have the same height as the room) and the like are not taken into account; in the calculation they are __not__ deducted for simplification. They are thus treated as if they did not exist (= air space).|**Rafters, | + | |
- | |The volume of window reveals (see Figure | + | |
- | + | ||
- | [{{: | + | |
- | + | ||
- | \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ | + | |
- | \\ | + | |
- | \\ | + | |
- | + | ||
- | |**Stairs**\\ The volume of a stairwell is part of the air volume and is fully taken into account. The volume of the stairs themselves (building | + | |
- | |The volume of elevator shafts and any other kind of shafts inside the thermal | + | |
An overview of the distinctions between the VL value from the PHPP and the Vn50 value for the blower door measurement can be found [[planning: | An overview of the distinctions between the VL value from the PHPP and the Vn50 value for the blower door measurement can be found [[planning: |