planning:airtight_construction:airtightness_measurements_in_passive_houses
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
planning:airtight_construction:airtightness_measurements_in_passive_houses [2021/07/30 09:57] – speper | planning:airtight_construction:airtightness_measurements_in_passive_houses [2023/01/30 11:44] (current) – [2. Calculation of volumes] zbastian | ||
---|---|---|---|
Line 1: | Line 1: | ||
- | |||
- | {{: | ||
- | \\ | ||
- | |||
- | |||
====== Airtightness measurements in Passive Houses ====== | ====== Airtightness measurements in Passive Houses ====== | ||
===== Instructions for carrying out measurements ===== | ===== Instructions for carrying out measurements ===== | ||
- | Airtightness measurements in Passive House buildings are to be carried out uniformly worldwide according to ISO 9972, procedure | + | Airtightness measurements in Passive House buildings are to be carried out uniformly worldwide according to ISO 9972, method |
- | The calculation of the reference volume for passive houses is to be carried out according to the procedure listed below which is not part of the ISO 9972. The resulting volume is to be used for the determination of the n50 value. \\ | + | The calculation of the reference volume for passive houses is to be carried out according to the procedure listed below which is not part of the ISO 9972. The resulting volume is to be used for the determination of the n< |
- | For the calculation and documentation, | + | For the calculation and documentation, |
==== 1. Comparison of designations ==== | ==== 1. Comparison of designations ==== | ||
Line 16: | Line 11: | ||
The superseded standards EN 13829 and the current ISO 9972 use different designations in some places. For a better overview, the most important ones are compared here: | The superseded standards EN 13829 and the current ISO 9972 use different designations in some places. For a better overview, the most important ones are compared here: | ||
- | [{{ :picprivate: | + | [{{ :picopen: |
- | + | ||
- | For measurements in Passive House buildings, the designation in accordance with EN 13829 should continue to be used. | + | |
==== 2. Calculation of volumes ==== | ==== 2. Calculation of volumes ==== | ||
- | |The air volume V< | + | The air volume V< |
- | |**Note: | + | |
- | |Irrespective of the degree of completion of the building, **the dimensions used should | + | |
- | |**A full and comprehensible room-by-room | + | |
- | + | ||
- | + | ||
- | [{{:picopen: | + | |
- | + | ||
- | \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ | + | |
- | + | ||
- | The **total air volume** within the thermal envelope will thus be taken into account. Special features are shown in Figure 2 for more detailed explanation. | + | |
- | + | ||
- | [{{: | + | |
- | \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ | + | |
- | |Visible rafters, beams, plasterboard encasings, wall-mounted installations (if these do not have the same height as the room) and the like are not taken into account; in the calculation they are __not__ deducted for simplification. They are thus treated as if they did not exist (= air space).|**Rafters, | + | |
- | |The volume of window reveals (see Figure | + | |
- | + | ||
- | [{{: | + | |
- | + | ||
- | \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ | + | |
- | \\ | + | |
- | \\ | + | |
- | + | ||
- | |**Stairs**\\ The volume of a stairwell is part of the air volume and is fully taken into account. The volume of the stairs themselves (building | + | |
- | |The volume of elevator shafts and any other kind of shafts inside the thermal | + | |
An overview of the distinctions between the VL value from the PHPP and the Vn50 value for the blower door measurement can be found [[planning: | An overview of the distinctions between the VL value from the PHPP and the Vn50 value for the blower door measurement can be found [[planning: | ||
Line 64: | Line 33: | ||
|The only exceptions may be temporarily taping over openings for missing building components, as described above, which affect the airtightness (e.g. missing door sill, missing odour trap in the waste water pipe). Again, an exact record should be kept about such sealing.|**Exception: | |The only exceptions may be temporarily taping over openings for missing building components, as described above, which affect the airtightness (e.g. missing door sill, missing odour trap in the waste water pipe). Again, an exact record should be kept about such sealing.|**Exception: | ||
|**The aim is to obtain realistic results reflecting the building’s airtightness in use, rather than to create an " | |**The aim is to obtain realistic results reflecting the building’s airtightness in use, rather than to create an " | ||
- | |**Negative AND excess pressure measurement**\\ Unlike in the EN 13829 and ISO 9972 standards, both negative pressure AND excess pressure are generally required when measuring the airtightness in Passive Houses. In this way, the reliability of the measurement results is significantly improved, with a minimum of extra effort. Finally, the airtightness parameter of the building is determined as an average value from the negative and excess pressure results.|**Measurement with negative __and__ excess pressure**| | + | |**Negative AND excess pressure measurement**\\ Unlike in the ISO 9972 standards, both negative pressure AND excess pressure are generally required when measuring the airtightness in Passive Houses. In this way, the reliability of the measurement results is significantly improved, with a minimum of extra effort. Finally, the airtightness parameter of the building is determined as an average value from the negative and excess pressure results.|**Measurement with negative __and__ excess pressure**| |
==== 5. Special features of large buildings (qE50-value) ==== | ==== 5. Special features of large buildings (qE50-value) ==== | ||
- | |In large buildings it is necessary to calculate the airtightness value with reference to the envelope area (q< | + | |In large buildings it is necessary to calculate the airtightness value with reference to the envelope area (q< |
|Buildings with an air volume V< | |Buildings with an air volume V< | ||
- | |For such large buildings, as a result __both__ values, i.e. the n50-value and the q50-value, will then need to be indicated in the measurement report.|**n< | + | |For such large buildings, as a result __both__ values, i.e. the n< |
- | |**Instructions regarding the procedure for calculating the envelope area according to EN 13829 and ISO 9972:**\\ The envelope area is the total area of all floors, walls and ceilings enclosing the volume under consideration, | + | |**Instructions regarding the procedure for calculating the envelope area according to ISO 9972:**\\ The envelope area is the total area of all floors, walls and ceilings enclosing the volume under consideration, |
- | [{{: | + | [{{: |
\\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ | \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ | ||
|In terraced houses, the partition walls of the building also count as the envelope area; in apartments in multi-storey buildings this also applies to all floors, walls and ceilings adjoining neighbouring apartments. These areas must only be taken into account if each accommodation unit is measured separately.|**Terraced houses and multi-storey buildings**| | |In terraced houses, the partition walls of the building also count as the envelope area; in apartments in multi-storey buildings this also applies to all floors, walls and ceilings adjoining neighbouring apartments. These areas must only be taken into account if each accommodation unit is measured separately.|**Terraced houses and multi-storey buildings**| | ||
- | |**Recommended target value for the q< | + | |**Recommended target value for the q< |
- | |__Note:__ In smaller buildings, more meticulous airtightness measures may be necessary in order to meet the n50 < 0.6 h-1 requirement. Compliance with the q< | + | |__Note:__ In smaller buildings, more meticulous airtightness measures may be necessary in order to meet the n< |
===== See also ===== | ===== See also ===== | ||