The following calculation illustrates the **heating load** Passive House requirement: | The following calculation illustrates the **heating load** Passive House requirement: | ||
\\ | \\ | ||
- | To ensure good indoor air quality, one needs about 30 m³ of fresh air per hour. This supply air can only be heated up to 50°C to avoid the scorching of dust. The specific heat capacity of air is 0.33 Wh/(m³K) at normal pressure and a temperature of approx. 21°C (comfort, see ISO 7730). From this follows:\\ | + | To ensure good indoor air quality, one person |
\\ | \\ | ||
|**30 m< | |**30 m< | ||
Line 41: | Line 41: | ||
\\ | \\ | ||
- | Some critics came up stating "there can't be one size for every site". This statement is correct, it is already anticipated in the criterea: That is, why passive house is a functional standard rather than a descriptive one. Of course the criteria lead to different | + | Some critics came up stating "there can't be one size for every site". This statement is correct, it is already anticipated in the criteria: That is, why passive house is a functional standard rather than a descriptive one. Of course the criteria lead to different |
\\ | \\ | ||